Field Testing the MagnaDrive Coupling Speed Control Technology on Northwest Industrial Applications
Report on HVAC Field Test Site
The 55-story Washington Mutual Tower is one of downtown
Seattle’s premier office buildings, with over 1 million square feet
of tenant space and a six-level underground parking garage. The
building is managed by Wright Runstad & Company, a major
developer and manager of office properties in the Northwest. In
cooperation with the Northwest Energy Efficiency Alliance, they
installed the MagnaDrive Coupling on both chilled water and
cooling tower pumps in the Washington Mutual Tower.
Application Overview
MagnaDrive installed two coupling applications in the Washington
Mutual Tower. One is a 125 HP 1800 RPM vertical solid shaft motor
running a centrifugal chilled water pump. This pump circulates
chilled water for 33 floors of the building. A thermostat, control
valve and heat exchanger utilize the chilled water to maintain a
comfortable temperature on each floor. Warm water leaving the
floor’s heat exchanger is circulated back down to the chiller and re-cooled.
Water flow through the chiller is regulated by a hand valve
on the pump discharge to maintain a constant pressure. The motor
load was 65 kW operating with the partially closed hand valve.
The other installation is on a 75 HP 1800 RPM vertical solid shaft
motor running a centrifugal condenser pump. This pump circulates
water between the chiller and a cooling tower. The pump runs at
full speed, and a hand valve on the discharge of the pump was set
to provide sufficient flow for the greatest
building demand. Power demand for this
pump motor with the valve restricted was
38 kW.
Manual throttling and fixed valve set
points that were used on both chilled
water and condenser pumps resulted
in wasted energy.
Other issues included high maintenance
costs associated with vibration and
cavitation in the pumps, and the need for
electronic soft start equipment to mitigate
start-up spikes in the pump motors that
can cause overheating and degradation of
motor insulation, as well as voltage sags
that can disrupt sensitive electronic
equipment in the building.
“ We don't have to replace couplings
annually and deal with aligning the
pumps and motors. The cavitation noise
we lived with for ten years disappeared
as soon as we started the MagnaDrive
Coupling. ”
Jeff Kasowski, Chief Engineer
Test Site
Washington Mutual Tower
Seattle, Washington
Field test site for MagnaDrive Coupling
HVAC application.
Problem
Throttling of chiller and cooling tower pumps
wasted energy.
Vibration and cavitation resulted in high
maintenance costs.
Electronic soft start equipment was needed
to mitigate the start-up spikes of the motors
which could cause motor overheating,
degradation of insulation, and voltage sags.
Solution
Two MagnaDrive Couplings were installed on
a vertical solid shaft chilled water pump and
condenser pump. The control system was
programmed to allow precise control of flow
rates, eliminate use of control valves, and reduce
the harmful vibration and cavitation.
Benefits
Maximum energy demand savings of 66%
on the condenser pump motor and 31% on
the chilled water pump motor were achieved
through system control with the MagnaDrive
Coupling.
Vibration and cavitation were eliminated,
reducing noise and maintenance costs.
Duration of locked rotor current on start-up
was reduced significantly, prolonging motor
life and eliminating the possibility of voltage
sags that disrupt electronic equipment.
Impressive Results with the MagnaDrive Couplings
Two MagnaDrive Couplings were installed, one on the condenser
pump and one on the chilled water pump. The customer’s control
system was programmed to automate coupling operation to provide
precise flow or pressure control via a 4-20 mA signal. Power
demand reductions follow:
Condenser Pump – The 75 hp condenser water pump moves cool
water through the chiller compressor removing heat from the
refrigerant via a heat exchanger. The warm water is then circulated
through the cooling tower heat exchanger and back to the chiller .
Prior to the MagnaDrive installation, the pump was always operated
at full speed and a hand valve was placed in a restricted position.
At this setting, the energy demand for the pump with the valve
restricted was a constant 38 kW . After the MagnaDrive installation,
the condenser pumps approximately 2000GPM with an energy
demand of 13 kW , which is a reduction of 66% (see Figure 1).
Chilled Water Pump - After the MagnaDrive Coupling was installed
on the 125 HP chilled water pump, the speed of the pump was
slowed to achieve a constant chilled water pressure for optimum
performance. Eliminating the hand valve on the discharge of the
pump reduced power demand from 65 kW to 45 kW , representing a
constant improvement of 20 kW , a reduction of 31%.
Washington Mutual operates their HVAC cooling system for eight
hours per day approximately one hundred days per year for a
savings of 36,000 kWh per year . A continuously operating system
could save up to 394,200 kWh per year.
Condenser Water Pump (Figure 1) Figure 1 shows demand in kW versus
flow rate in gallons per minute for the
condenser pump. The data was developed
by measuring the actual power draw and
water flow of the W ashington Mutual T ower
system over a wide range of potential
operations. In practice, 2000 GPM is the
flow used during condenser operations.
The power required drops 25 kW at this
flow rate, a 66% reduction in power .
The MagnaDrive Couplings were
programmed to start the motors uncoupled
from the pumps, significantly reducing the
start-up current duration and peak
compared to the old electronic soft start
systems. (See Figures 2 and 3). The high
amperage levels occurring throughout the
start-up period caused heating in the
motors, potentially degrading motor
insulation and shortening motor life.
High amperage draw can also cause voltage
sags in the building. V oltage sags can
disrupt sensitive equipment such as
computer systems, a serious problem in
a large office tower .
Condenser Water Pump (Figure 2)
Chilled Water Pump (Figure 3)
Figures 2 and 3 show across the line
starting curves for the motors. The dashed
blue lines depict starting the motors with
the loads coupled through elastomeric
couplings using an electronic soft start.
The red lines represent the motors starting
uncoupled through the MagnaDrive
Couplings using electronic soft starts. The
original purpose of the electronic soft start
was to reduce the amplitude of locked rotor
current when starting the motors rigidly
coupled to the pumps. As shown, when the
electronic soft start timed out, the customer
still experienced a 280 Amp spike on the
condenser pump motor , and 475 Amps on
the chilled water pump motor . Use of the
MagnaDrive Coupling and the electronic
soft start together eliminates the excessive
current spikes and reduces the duration of
locked rotor current by 4 seconds.
“MagnaDrive came at a perfect time.
W e were looking into a V ariable
Frequency Drive, but we had a problem
finding room for it, we were worried
about the harmonics and filtering devices
we would have to add, not to mention
powering up a VFD that large and the
inevitable extra heat loads. Then came
the MagnaDrive. The large footprint isn’t
needed, harmonics aren't an issue, no
power is required, and the control is
better than imagined.”
Jeff Kasowski, Chief Engineer
How the MagnaDrive Coupling Operates
The MagnaDrive Coupling operates on the
principle of magnetic induction. It consists
of two independent components that have
no physical contact. A precision rotor
assembly containing high-energy permanent
magnets is mounted on the load shaft. A
conductor assembly with copper rings is
connected to the motor shaft. Relative
motion between the magnets and copper
rings creates a magnetic field that transmits
torque through the air gap between the
coupling’s components. Varying the width of
the gap changes the coupling force,
producing a controlled and infinitely
variable output speed.